The Use of Averaged-Value Model of Modular Multilevel Converter in DC Grid
作者:管理员    发布于:2015-04-07 22:45:08    文字:【】【】【
摘要:Xu, J.; Gole, A.M.; Zhao, C., "The Use of Averaged-Value Model of Modular Multilevel Converter in DC Grid," Power Delivery, IEEE Transactions on , vol.30, no.2, pp.519,528, April 2015
This paper investigates the applicability of averaged-value models (AVMs) formodular multilevel converters (MMCs) operating in a voltage-sourced converter-based-high-voltage dc (VSC-HVDC) grid. The AVM models are benchmarked by comparison with a detailed electromagnetic transient model of the grid, including a fully detailed MMC model. Analysis results show that the AVM is only effective as long as the capacitors are large enough to maintain nearly constant voltage across each MMC submodule. This paper also shows that previously developed MMC averaged models are not able to accurately simulate the transients under dc fault conditions. This paper introduces topology changes to a previously proposed averaged model that results in much improved simulation for such conditions. This paper also shows that the model can be used effectively to study HVDC grids with significant time savings.